| Characteristics |
 |
Value |
| Input max. (heating) |
 |
120 kW |
| Input min. (heating) |
 |
22 kW |
| Output power max. (80/60°C) |
 |
116,6 kW |
| Output power min. (60/80°C)) |
 |
21,6 kW |
| Efficiency at 30% load (EN677) |
 |
108 % |
| Capacity (total) |
 |
28 L |
| CO emissions (max./min. output) |
 |
77/2 (G20) mg/kWh |
| NOx emissions (max./min. output) |
 |
70/26 (G20) mg/kwh |
| Chimney: Max.pressure drop in flue pipe |
 |
150 Pa |
| Flue gas temperature at max.output 80/60°C |
 |
83 °C |
| Mass rate of combustion products (gas) |
 |
114 Kg/h |
| Chimney connection Ø |
 |
100 mm |
| Chimney connection type |
 |
B23-B23P-C13-C33-C33S-C43-C53 |
| Gas supply pressure G20/25 |
 |
20-25 mbar |
| Gas supply pressure G30/31 |
 |
30-37-50 mbar |
| Gas flow rate G20 (max.output) |
 |
8,5 - 12,7 m³/h |
| Gas flow rate G25 (max.output) |
 |
9,8 (14,4) m³/h |
| Gas flow rate G31 (max.output) |
 |
3,3 (5,1) m³/h |
| CO2 (max / min output) G20/G25 |
 |
9,0-8,5 %CO2 |
| CO2 (max / min output) G31 |
 |
10,3-10 %CO2 |
| Air intake connection Ø |
 |
100 mm |
| Connection - gas |
 |
1" (M) Ø |
| Connection - heating (F) |
 |
1"1/2 (M) Ø |
| Water pressure drop boiler at Δt = 20°C |
 |
80 mbar |
| Dim. - Width or Diameter (w/o conn.) |
 |
632 mm |
| Dim. - Depth (w/o conn.) |
 |
535 mm |
| Dim. - Height (w/o conn.) |
 |
1000 mm |
| Max. operating temperature |
 |
90 °C |
| Max.service pressure heating (primary) |
 |
4 bar |
| Protection |
 |
IP30 |
| Operating voltage (50Hz) |
 |
230 V |
| Electrical power requirements |
 |
1,1 A |
| Weight (empty) |
 |
83 Kg |