ACV - excellence in hot water

Discover our solutions > JUMBO 1000


JUMBO 1000
Available documents
pdf HR-Jumbo : Sales brochure
 
Download centre
Presentation
 
N/A Floor installation Hot water heater [ key ]
 
  • High performance indirect water heater for floor installation, a guarantee of high hot water comfort
  • Mineral wool insulation
  • Control panel with thermometer and thermostat
  • Elegant oven lacquered steel covering
  • Casing delivered separately to allow the unit to pass through standard doorways (800 mm)




Main characteristics
 
Capacity (primary) (L) : 160
Capacity (total) (L) : 1000
Heating surface DHW tank (m²) : 5,5
Pressure drop (primary) (mbar) : 101
Primary flow (L/h) : 7800
Connection - primary (female) (Ø) : 2"
Connection - DHW (male) (Ø) : 2"
Connection - re-circulation / safety valve (Ø) : 2" (M)
Peak flow at 40 °C (L/10’) : 2265
Peak flow 1st hour at 40 °C (L/60') : 4940
Continuous flow at 40°C (L/h) : 3210
Peak flow at 45 °C (L/10’) : 1941
Peak flow 1st hour at 45 °C (L/60') : 4234
Continuous flow at 45 °C (L/h) : 2751
Peak flow at 60 °C (L/10’) : 1145
Peak flow 1st hour at 60 °C (L/60’) : 2438
Continuous flow at 60 °C (L/h) : 1562
Coefficient (NL) () : 87
Max. absorbed heat (Heat source: boiler) (kW) : 112
Max. operating temperature (°C) : 90
Max.service pressure heating (primary) (bar) : 5
Max.service pressure (DHW) (bar) : 10
Dim. - Width or Diameter (w/o conn.) (mm) : 1020
Dim. - Depth (w/o conn.) (mm) : 1020
Dim. - Height (w/o conn.) (mm) : 2315
Weight (empty) (Kg) : 380
 


Design characteristics
 

Design characteristics
Legend 
  1. Stainless steel inner tank
  2. Steel outer tank
  3. 120 mm thick mineral wool insulation
  4. Heating fluid inlet (primary)
  5. Heating fluid outlet (primary)
  6. Domestic cold water inlet (secondary)
  7. Domestic hot water outlet (secondary)
  8. Control thermostat
  9. Control thermometer
  10. Control thermostat bulb
  11. Bulb for control thermometer
  12. Air vent
  13. Metal casing
  14. DHW recirculation loop
 
 
Technical specifications (*)
 

Characteristics Value
 Capacity (primary)  160 L
 Capacity (total)  1000 L
 Heating surface DHW tank  5,5 m²
 Pressure drop (primary)  101 mbar
 Primary flow  7800 L/h
 Connection - primary (female)  2" Ø
 Connection - DHW (male)  2" Ø
 Connection - re-circulation / safety valve  2" (M) Ø
 Peak flow at 40 °C  2265 L/10’
 Peak flow 1st hour at 40 °C  4940 L/60'
 Continuous flow at 40°C  3210 L/h
 Peak flow at 45 °C  1941 L/10’
 Peak flow 1st hour at 45 °C  4234 L/60'
 Continuous flow at 45 °C  2751 L/h
 Peak flow at 60 °C  1145 L/10’
 Peak flow 1st hour at 60 °C  2438 L/60’
 Continuous flow at 60 °C  1562 L/h
 Coefficient (NL)  87
 Max. absorbed heat (Heat source: boiler)  112 kW
 Max. operating temperature  90 °C
 Max.service pressure heating (primary)  5 bar
 Max.service pressure (DHW)  10 bar
 Dim. - Width or Diameter (w/o conn.)  1020 mm
 Dim. - Depth (w/o conn.)  1020 mm
 Dim. - Height (w/o conn.)  2315 mm
 Weight (empty)  380 Kg

Output data
 

Characteristics Value
 Peak flow at 40 °C  2265 L/10’
 Peak flow 1st hour at 40 °C  4940 L/60'
 Continuous flow at 40°C  3210 L/h
 Peak flow at 45 °C  1941 L/10’
 Peak flow 1st hour at 45 °C  4234 L/60'
 Continuous flow at 45 °C  2751 L/h
 Peak flow at 60 °C  1145 L/10’
 Peak flow 1st hour at 60 °C  2438 L/60’
 Continuous flow at 60 °C  1562 L/h
 Coefficient (NL)  87
 Max. absorbed heat (Heat source: boiler)  112 kW

 

(*)
  • The product range offered can vary according to country. Please consult your distributor.
  • All values indicated on this site are provided for information only. Please refer to our legal notice.
  • The following operating conditions were used to generate hot water output data for our products:
    • Supply water: 10°C
    • Primary water: 80°C (boilers), 85°C (water heaters) or 90°C (HeatMaster)
  • Operating conditions
    Cold water: 10°C
    Delta T° (outlet) : 30°C
    Data provided are indicative only. Please read the complete disclaimer.
Disclaimer