Cylinders

HR

HR s 800

Stainless steel indirect cylinder for domestic hot water.

  • Tank-in-Tank
  • BIM Objects
  • Commercial

# GTIN : 5400891002032
# P/N : 06633001

  • External heating source
  • Tanks
  • Floor installation
  • Low maintenance with no anode protection required
  • Fast heat up and recovery using the unique tank-in-tank design
  • Low standing losses – cylinder comes with polyurethane foam insulation and hard-wearing polypropylene finish
  • Large heating surface area reduces boiler cycling
  • Reduces Legionella risk due to temperature: hot water stored at > 60°C
  • Long life – 25-year guarantee on the corrosion resistant stainless steel cylinder
  • Suitable for vented or unvented systems (optional unvented kit required)
  • Cost effective solution, simple installation with no de-stratification kit needed and no flue requirements
  1. DHW return or temp/pressure relief valve connection.
  2. Manual air vent.
  3. Cold water inlet connection.
  4. Rigid top case.
  5. Stainless steel thermostat pocket.
  6. 100mm flexible polyurethane foam insulation.
  7. Outer shell vinyl jacket.
  8. DHW return connection.
  9. Primary inlet connection.
  10. Internal stainless steel DHW tank.
  11. External Tank (primary) steel.
  12. Primary return connection.

Constructive characteristics

Capacity (total) 800 L
Capacity (primary) 125 L
Weight (empty) 261 kg
Max operating temperature 85 °C
Max operating pressure heating (primary) 4 bar
Max operating pressure (DHW) 8,6 bar
Primary flow (EN 12897:2016) 2,08 L/s
Connection - primary 2 F Ø"
Connection - DHW 1 ½ M Ø"
Connection - re-circulation / safety valve 1 ½ M Ø"

Heating characteristics

Reheat time (EN 12897) - min
Reheat performance (EN 12897:2016) 82 kW
Max absorbed heat (Heat source: boiler) 100 kW

Domestic hot water performance

Peak flow at 40°C 1881 L/10’
Peak flow 1st hour at 40°C 4270 L/60’
Continuous flow at 40°C 2868 L/h
Peak flow at 45°C 1612 L/10’
Peak flow 1st hour at 45°C 3660 L/60’
Continuous flow at 45°C 2458 L/h
Peak flow at 60°C 961 L/10’
Peak flow 1st hour at 60°C 2124 L/60’
Continuous flow at 60°C 1395 L/h
Coefficient (NL) 67
Dimensions A 1955 mm
Dimensions B 780 mm
Dimensions C 335 mm
Dimensions D 1585 mm
Dimensions E - mm
    • Technical brochure

    • Thermostat mounting kit

    • 494 KB –

    • Technical brochure

    • HRi 320, 600, 800 - Installation, operations and maintenance instructions

    • 1.94 MB – en

    • Technical brochure

    • HRs 321, 601, 800, 1000 / Jumbo 800, 1000 - Installation, operations and maintenance instructions

    • 2.45 MB – en

    • Marketing brochure

    • Jumbo 800 & 1000 Technical Manual UK

    • 2.45 MB – en

    • Marketing brochure

    • Product Guide 2019-20

    • 12.41 MB – en

Eco Design Fields

Standing loss (Energy label) 137 W
    • Product Fiche

    • HR s 800

Other products

HR s 1000
Cylinders

Stainless steel indirect cylinder for domestic hot water.

Call ACV

Need some answers? Talk to a specialist

Tel. +44 (0)1383 820100