Previous product
Portrait

Smart E 160

Stainless steel indirect cylinder for domestic hot water.

  • Tank-in-Tank
  • Domestic and Commercial
Short Energy Label
  • label_energy_EXT
  • label_energy_RES
  • Tanks
  • Floor installation
# GTIN : 5400891001783
# P/N : XB301600
Label 1
  • Low cost solution, simple installation with no de-stratification kit needed and no flue requirements.
  • Minimal standing losses – cylinder comes with polyurethane foam insulation and thick polypropylene jacket
  • Reduces legionella risk due to temperature: hot water stored at > 60°C
  • Low maintenance with no anode protection required
  • Fits through a standard doorway for access to plant room
  • 5-year warranty
  • Can easily be coupled to a condensing boiler
  • Simplified wiring with ‘plug and play’ electrical connection
  • Supplied with 3kW immersion heater (6kW option available)
  • Suitable for unvented systems – supplied as a complete package including 3.5 bar mains unvented kit
  • Maximise capacity of the cylinder with DHW mixing valve and 2 port valve supplied as standard
Schematic
  1. Auxilliary connection DHW
  2. Domestic cold water inlet connection
  3. Flow connection (primary circuit)
  4. Polypropylene chell
  5. Internal stainless steel tank.
  6. Return connection (primary circuit)
  7. Immersion heater connection
  8. Primary air vent
  9. Hot water outlet connection
  10. Rigid polypropylene top cover
  11. Thermostat pocket
  12. Polyurethane foam insulation
  13. Outer steel tank (primary circuit)
  14. Polypropylene base

Constructive characteristics

Smart E 130 Smart E 160
Capacity (total) L 130 161 L
Capacity (primary) L 55 62 L
Weight (empty) kg 45 54 kg
Max operating temperature °C 90 90 °C
Max operating pressure heating (primary) bar 3 3 bar
Max operating pressure (DHW) bar 8,6 8,6 bar
Primary flow (EN 12897:2016) L/s 0,70 0,70 L/s
Primary heater pressure drop (EN12897:2016) mbar 26,8 26,8 mbar
Connection - primary Ø" 1 F 1 F Ø"
Connection - DHW Ø" 3/4 M 3/4 M Ø"
Connection - re-circulation / safety valve Ø" 3/4 M 3/4 M Ø"
Connection - heating element Ø" 1 ½ F 1 ½ F Ø"

Heating characteristics

Smart E 130 Smart E 160
Reheat time (EN 12897:2016) min 10 10 min
Reheat performance (EN 12897:2016) kW 18,4 24,7 kW
Heating time from 10 to 60°C - 6 kW (3 kW) min 78 (157) 97 (193) min
Max absorbed heat (Heat source: boiler) kW 23 31 kW

Domestic hot water performance

Smart E 130 Smart E 160
Peak flow at 40°C L/10’ 236 321 L/10’
Peak flow 1st hour at 40°C L/60’ 784 1063 L/60’
Continuous flow at 40°C L/h 658 890 L/h
Peak flow at 45°C L/10’ 202 275 L/10’
Peak flow 1st hour at 45°C L/60’ 672 911 L/60’
Continuous flow at 45°C L/h 564 763 L/h
Peak flow at 60°C L/10’ 117 161 L/10’
Peak flow 1st hour at 60°C L/60’ 384 549 L/60’
Continuous flow at 60°C L/h 320 465 L/h
Coefficient (NL) 1,0 2,1

Eco Design Fields

Smart E 130 Smart E 160
Energy efficiency storage class B B
Standing loss (Energy label) W 40 47 W
Energy Label EU
Energy Label UK
Product Fiche
Smart E 130 Smart E 160
Dimensions A (mm) 1024 1225 (mm)
Dimensions B (mm) 759 959 (mm)
Dimensions C (mm) 525 725 (mm)
Dimensions D (mm) - - (mm)

Technical brochure

Smart 320 420 600 800

1.54MB – en

Smart E 130 Data Sheet

167.05kB – en

Smart Green 130, 160, 210 - Installation, operation and maintenance instructions

1.58MB – en

Smart SLE130, 160, SLE+210, 240, 300 - Installation, operation and maintenance instructions

861.23kB – en

Smartline SLE Plus Technical Manual UK

514.18kB – en

Marketing brochure

ACV UK Product Guide

9.61MB – en

Ecodesign

Energy Label EU

Energy Label UK

Product Fiche

BIM Files

BIM Files

Call ACV

Need some answers? Talk to a specialist

Tel. +44 (0)1383 820100