Water Heaters

WaterMaster

WaterMaster 45

Condensing domestic hot water heater

  • Available in Natural gas and LPG
  • TANK-IN-TANK TECHNOLOGY
  • Also available in 70-85-120kW.

# A1002671

  • Gas
  • Hot Water Heater
  • Standard
  • Concentric
  • Floor installation
  • Certified EN89 - Ecodesign Lot 2 (EN 812/2013 - EN 814/2013)
  • Equipped with ACVMax burner and modbus controls
  • Condenses in hot water mode
  • Delivers an exceptional peak and continuous volume of hot water
  • Stainless Steel domestic hot water tank - no anode protection required
  • Space saving footprint - reduced plant-room space requirement
  • Stainless steel heat exchanger reduces maintenance and increases system lifespan
  • Multiple units can be grouped in cascade for larger applications or back up
  1. ACVMax Control panel
  2. NTC sensor (primary circuit)
  3. High efficiency circulator pump
  4. Condensate recovery dish
  5. Electrical panel (with spare fuses at the back)
  6. “Tank-in-Tank” hot water production tank
  7. Flue gas exhaust tube
  8. Indirect water pre-heater
  9. Primary circuit
  10. Pressure sensor

Constructive characteristics

Capacity (total) 196 L
Capacity (primary) 100 L
Capacity (domestic hot water) 96 L
Coil capacity 0 L
Chimney: Max pressure drop in flue pipe 130 Pa
Chimney: max length of concentric flue pipe 20 m
Chimney connection 80/125 Ømm
Connection - heating 1 F Ø"
Connection - DHW 1 M Ø"
Connection gas 3/4 M Ø"
Connection - safety valve 1/2M Ø"
Max operating temperature 87 °C
Water pressure drop boiler at Δt = 20°C 10 mbar
Max service pressure heating (primary) 3 bar
Max service pressure (DHW) 8,6 bar
Height when tilted 1855 mm
Weight (empty) 177 kg

Heating characteristics

Pre-heating time from 10 to 80°C (Heat source: boiler) 23 min
Reheat time from 40 to 90°C 25 min
Reheat time from 40 to 80°C 16 min
Heating time from 10 to 90°C 30 min

Combustion

Input max (heating) HCV 50,0 kW
Input max (heating) LCV 45 kW
Combustion efficiency 97,9 %
Efficiency DHW mode ΔT 30K 103,1 %
Efficiency DHW mode (EN89) 108,5 %
CO emissions max output 63 ppm
CO emissions min output 4 ppm
Mass rate of combustion products (gas) 76 kg/h
NOx class (EN483) 5
Gas flow rate (min output) 0,9 m³/h

Eco Design Fields

NOx weighted (GCV) 30,2 mg/kWh

Domestic hot water performance

Peak flow at 40°C 451 L/10’
Peak flow 1st hour at 40°C 1610 L/60’
Continuous flow at 40°C 1390 L/h
Peak flow at 45°C 373 L/10’
Peak flow 1st hour at 45°C 1366 L/60’
Continuous flow at 45°C 1192 L/h
Peak flow at 60°C 320 L/10’
Peak flow 1st hour at 60°C 894 L/60’
Continuous flow at 60°C 820 L/h

Electrical Characteristics

Voltage 230 V
Frequency 50 Hz
Protection IP 30
Electrical consumption 126 W
Electrical power requirements 0,85 A
    • Technical brochure

    • ACVMax - Installers handbook for heating systems controlled with ACVMax

    • 25.55 MB – en

    • Technical brochure

    • WaterMaster 25 / 35 / 45 / 70 / 85 / 120 - Installation, Operation and Maintenance Instructions for the Installer and the User

    • 14.41 MB – en

    • Technical brochure

    • WaterMaster 25 / 35 / 45 / 70 / 85 / 120 - Инструкция по установке, эксплуатации и сервисному oбслуживанию, для пользователя и сервисного специалиста

    • 13.10 MB – ru

    • Marketing brochure

    • WaterMaster - EN 89 Certified Storage Water Heater

    • 676 KB – en

Eco Design Fields

Water heating energy efficiency [ηwh] (EU 814/2013 Art 2 (15) Ann.IV-3) 87,2 %
Declared load profile L
Water heating energy efficiency class A
Sound power level indoors LWA 59 dB
    • Energy Label

    • WaterMaster 45

    • Product Fiche

    • WaterMaster 45

Other products

WaterMaster 85
Water Heaters
WaterMaster 35
Water Heaters
WaterMaster 70
Water Heaters
WaterMaster 120
Water Heaters
Find an installer

Get in touch with an installer for a free, no obligation estimate.

Call ACV

Need some answers? Talk to a specialist

Tel. +32 2 334 82 20