Condensing

Compact Condens

Compact Condens 210

High output floor gas condensing boiler for industrial applications

# A1002890

  • Gas
  • Boilers
  • Standard
  • Floor installation
  • Condensing boiler: maximum recovery of energy (107.5% efficiency) from the flue gas.
  • Heat exchanger in aluminum
  • Compact dimensions, small footprint (0,8m²) for relatively high powers.
  • Available in 8 models ranging from 170 to 600 kW.
  • Operating simplicity: Maxsys climate controller with LCD display. Integrated DHW module.
  • Easy connection of one or more heating circuits (high or low temperature) or 1 DHW circuit.
  • Ideal to be cascaded up to 1200 kW.
  1. Chimney connection Ø200
  2. Auto air vent
  3. Fan
  4. Heating return (+ filling valve and water pressure sensor)
  5. Air inlet (Ø110)
  6. Venturi
  7. MAXSys Controller
  8. Gas valve
  9. Control panel with display and pressure gauge
  10. Heating supply
  11. Flame sight glass
  12. Ignition and ionization electrodes (2x)
  13. C1 and C2 terminal strips for electrical connections
  14. Air pressure switch (backside)
  15. Inspection sump cover
  16. Cast aluminium heat exchanger
  17. Condensate trap
  18. Inspection cover
  19. Gas pipe

Constructive characteristics

Capacity (total) 21,3 L
Capacity (primary) 21,3 L
Chimney: Max pressure drop in flue pipe 150 Pa
Chimney connection 200 Ømm
Air intake connection 110 Ømm
Connection - heating 2 M Ø"
Connection gas 1 M Ø"
Primary flow 9000 L/h
Max operating temperature 85 °C
Max service pressure heating (primary) 6 bar
Pressure drop (primary - ΔT10K) 96 mbar
Weight (empty) 217 kg

Combustion

Input max (heating) HCV 233,1 kW
Input max (heating) LCV 210 kW
Efficiency at 30% load (EN677) 107,5 %
Efficiency at 100% load (50/30°C) 102,8 %
Efficiency (max output) 80/60°C 97,4 %
Efficiency (min output) 80/60°C 97 %
CO emissions max output 41,8 ppm
NOx weighted (GCV) 50 mg/kWh
NOx class (EN483) 5
Output power max (80/60°C) 204,5 kW
Output power min (80/60°C) 40,7 kW
Gas flow rate (min output) 4,36 m³/h

Electrical Characteristics

Voltage 230 V
Frequency 50 Hz
Protection IP 00B
Electrical consumption 1150 W
Electrical power requirements 5 A
    • Technical brochure

    • INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS for the Installer and the User Compact Condens 340 - 425 - 510 - 600

    • 7.36 MB – en

    • Technical brochure

    • Compact Condens - Installation, operation and maintenance instructions

    • 7.19 MB – en

    • Technical brochure

    • Compact Condens - Addendum chimney calculation

    • 132 KB –

    • Marketing brochure

    • Compact Condens 170 / 210 / 250 / 300

    • 1.95 MB – en

Eco Design Fields

Space heating energy efficiency class A
Seasonal space heating efficiency 92,1 %
Sound power level indoors LWA 70 dB
    • Product Fiche

    • Compact Condens 210

Other products

Compact Condens 425
Condensing
Compact Condens 170
Condensing
Compact Condens 300
Condensing
Compact Condens 250
Condensing
Find an installer

Get in touch with an installer for a free, no obligation estimate.

Call ACV

Need some answers? Talk to a specialist

Tel. +32 2 334 82 20