Previous product Next product
Portrait

Smart E 160

Fast recovery floor standing Tank-in-Tank Cylinder. Connection for an optional electrical resistance in the primary circuit.

  • TANK-IN-TANK TECHNOLOGY
Short Energy Label
  • label_energy_EXT
  • label_energy_RES
  • Tanks
  • Floor installation
# GTIN : 5400891001783
# P/N : 06618901
Label 2
  • 3 kW or 6 kW Immersion heater as option available
  • Low Heat Loss - 50mm Polyurethane insulation
  • Deluxe, thick - shock resistant - polypropylene jacket.
  • Stainless steel domestic cylinder
  • Anti-Legionella : Storage temperature > 60°C.
Schematic
  1. Auxilliary connection DHW
  2. Domestic cold water inlet connection
  3. Flow connection (primary circuit)
  4. Polypropylene chell
  5. Internal stainless steel tank.
  6. Return connection (primary circuit)
  7. Immersion heater connection
  8. Primary air vent
  9. Hot water outlet connection
  10. Rigid polypropylene top cover
  11. Thermostat pocket
  12. Polyurethane foam insulation
  13. Outer steel tank (primary circuit)
  14. Polypropylene base

Constructive characteristics

Smart E 130 Smart E 160 Smart E 210 Smart E 240 Smart E 300
Capacity (total) L 130 161 203 242 293 L
Capacity (primary) L 55 62 77 78 93 L
Weight (empty) kg 45 54 66 76 87 kg
Max operating temperature °C 90 90 90 90 90 °C
Max operating pressure heating (primary) bar 3 3 3 3 3 bar
Max operating pressure (DHW) bar 8,6 8,6 8,6 8,6 8,6 bar
Primary flow (EN 12897:2016) L/s 0,70 0,70 1,25 1,25 1,25 L/s
Primary heater pressure drop (EN12897:2016) mbar 26,8 26,8 41,6 47,3 52,4 mbar
Connection - primary Ø" 1 F 1 F 1 F 1 F 1 F Ø"
Connection - DHW Ø" 3/4 M 3/4 M 3/4 M 3/4 M 3/4 M Ø"
Connection - re-circulation / safety valve Ø" 3/4 M 3/4 M 3/4 M 3/4 M 3/4 M Ø"
Connection - heating element Ø" 1 ½ F 1 ½ F 1 ½ F 1 ½ F 1 ½ F Ø"

Heating characteristics

Smart E 130 Smart E 160 Smart E 210 Smart E 240 Smart E 300
Reheat time (EN 12897:2016) min 10 10 9 9 9 min
Reheat performance (EN 12897:2016) kW 18,4 24,7 32,2 39,2 44,6 kW
Heating time from 10 to 60°C - 6 kW (3 kW) min 78 (157) 97 (193) 122 (243) 145 (290) 175 (350) min
Max absorbed heat (Heat source: boiler) kW 23 31 39 53 68 kW

Domestic hot water performance

Smart E 130 Smart E 160 Smart E 210 Smart E 240 Smart E 300
Peak flow at 40°C L/10’ 236 321 406 547 800 L/10’
Peak flow 1st hour at 40°C L/60’ 784 1063 1349 1820 2360 L/60’
Continuous flow at 40°C L/h 658 890 1132 1527 2100 L/h
Peak flow at 45°C L/10’ 202 275 348 469 640 L/10’
Peak flow 1st hour at 45°C L/60’ 672 911 1156 1560 1920 L/60’
Continuous flow at 45°C L/h 564 763 970 1309 1710 L/h
Peak flow at 60°C L/10’ 117 161 209 272 370 L/10’
Peak flow 1st hour at 60°C L/60’ 384 549 689 913 1100 L/60’
Continuous flow at 60°C L/h 320 465 576 769 970 L/h
Coefficient (NL) 1,0 2,1 3,0 5,2 11,8

Eco Design Fields

Smart E 130 Smart E 160 Smart E 210 Smart E 240 Smart E 300
Energy efficiency storage class B B B B B
Standing loss (Energy label) W 40 47 54 59 69 W
Energy Label
Product Fiche
Smart E 130 Smart E 160 Smart E 210 Smart E 240 Smart E 300
Dimensions A (mm) 1024 1225 1493 1741 2043 (mm)
Dimensions B (mm) 759 959 332 337 405 (mm)
Dimensions C (mm) 525 725 1229 1477 1780 (mm)
Dimensions D (mm) - - 374 374 405 (mm)

Technical brochure

Electrical connection heating elements 10800081 to 10800084 - Weerstand - Résistance - Immersion Heater

1.18MB – fr en nl it de es

Smart / Smart EW - Addendum for primary connections

83.64kB – en

Smart 320 420 600 800

1.54MB – en

Smart E (Plus) - Installation, operations and maintenance instructions

1.82MB – en

Smartline SLE Plus Technical Manual UK

514.18kB – en

Marketing brochure

Smart

23.94MB – en

ACV Guide to Ecodesign and Energy Labelling

969.34kB – en

Ecodesign

Energy Label

Product Fiche

BIM Files

BIM Files

Find an installer

Get in touch with an installer for a free, no obligation estimate.

Call ACV

Need some answers? Talk to a specialist

Tel. +32 2 334 82 20