LCA HP 2000 hh

Enamelled tank with single exchanger designed for the production of Domestic Hot Water from a heating application such as a boiler, Heat Pump or Solar Panels

# 06639701

  • External heating source
  • Add-on electricity
  • Solar
  • Tanks
  • Floor installation
  • One very high capacity coil.
  • Enamelled tank high quality resistant to thermal shock and high temperatures.
  • DHW output at the highest point of the tank.
  • Three side connections 2 ".
  • Protection anodes magnesium side.
  • Flange Ø 110 or Ø 400 (from 750 L) for the inspection of the interior of the tank and the installation of immersion heaters (optional).
  • Drain centered at the lowest point for a total evacuation.
  • Glass wool insulation 100mm classified M1 (non-flammable) with gray envelope flame retardant flexible PVC.
  • Also available with 400mm Manhole. Please contact our sales office for prices.


  1. Check hot water.
  2. Handling ring.
  3. Large coil surface.
  4. Connection for magnesium anode protection.
  5. Removable legs for transport.
  6. Manhole Ø110/Ø400.
  7. *Health connection.*


Capacity (total) 2000 L
Heating surface coil 10,0
Coil capacity 76,0 L
Connection - primary - inches
Connection - DHW 2 F inches
Connection - coil 6/4 F inches
Primary flow (ΔT10K) do not use 6100 L/h
Pressure drop coil 781 mbar
Max operating temperature (primary) 95 °C
Max operating pressure (DHW) 7 bar
Max operating pressure (primary) - bar
Max operating pressure (coil) 7 bar
Weight (empty) 510 kg

Hot water performances

Continuous flow at 60°C 1931 L/h
Power max. coil (45/40°C) ΔT 30K 35 kW
A 580 mm
B 2261 mm
C 1888 mm
D 1244 mm
E 600 mm
F 200 mm
G 650 mm
H 1671 mm
J 600 mm
Dim. - Height (with conn.) 2293 mm
Diameter access hatch 110 mm
Dim. - Height (w/o conn.) 2261 mm
Dim. - Width or Diameter (w/o conn.) 1100 mm
Dim - Height when tilted 2518 mm

Other products

LCA 2CO 300 hh

Glass lined carbon steel tank with twin coil for DHW

LCA 2CO 500 hh

Glass lined carbon steel tank with twin coil for DHW

LCA 1000 hh

Carbon steel tank for primary network.

LCA 1500 mh

Carbon steel tank for primary network.

Find an installer

Get in touch with an installer for a free, no obligation estimate.

Call ACV

Need some answers? Talk to a specialist