Previous product
Portrait

Jumbo 1000

Fast recovery, high volume Tank-in-Tank hot water storage

  • TANK-IN-TANK TECHNOLOGY
  • For industrial applications
  • label_energy_EXT
  • Tanks
  • Floor installation
# GTIN : 5400891002704
# P/N : 06648601
Label 2
  • Tank-in-Tank floor standing indirect hot water storage tank.
  • Stainless steel construction - no need for sacrificial anodes.
  • High performance - fast heat up and rapid recovery.
  • Fully insulated - 120mm Rock wool insulation.
  • Stove enameled steel casing, supplied seperatley to enable the tank to pass through standard 800mm doorways.
  • Two sizes - 800 and 1000 litres.
  • Can be used in battery formation for high output installations.
  • Large heating surface area means reduced boiler cycling.
  • Anti-Legionella : Storage temperature > 60 ° C.
Schematic
  1. Hot water outlet.
  2. Domestic cold water inlet.
  3. Thermometer.
  4. Control thermostat.
  5. Rockwool insulation - 120 mm.
  6. Stove enameled metal casing.
  7. Domestic Hot Water return /T+P Valve tapping
  8. Primary water flow connection
  9. Outer steel tank containing the primary fluid.
  10. Thermostat pocket
  11. Internal stainless steel tank.
  12. Primary water return connection

Constructive characteristics

Jumbo 800 Jumbo 1000
Capacity (total) L 800 1000 L
Capacity (primary) L 125 160 L
Weight (empty) kg 360 380 kg
Max operating temperature °C 85 85 °C
Max operating pressure heating (primary) bar 4 4 bar
Max operating pressure (DHW) bar 8,6 8,6 bar
Primary flow (EN 12897:2016) L/s 2,08 2,08 L/s
Primary heater pressure drop (EN12897:2016) mbar 75 60 mbar
Connection - primary Ø" 2 F 2 F Ø"
Connection - DHW Ø" 1 ½ M 1 ½ M Ø"
Connection - re-circulation / safety valve Ø" 1 ½ M 1 ½ M Ø"

Heating characteristics

Jumbo 800 Jumbo 1000
Reheat time (EN 12897) min - - min
Reheat performance (EN 12897:2016) kW 82 97 kW
Max absorbed heat (Heat source: boiler) kW 100 112 kW

Domestic hot water performance

Jumbo 800 Jumbo 1000
Peak flow at 40°C L/10’ 1881 2265 L/10’
Peak flow 1st hour at 40°C L/60’ 4270 4940 L/60’
Continuous flow at 40°C L/h 2868 3210 L/h
Peak flow at 45°C L/10’ 1612 1941 L/10’
Peak flow 1st hour at 45°C L/60’ 3660 4234 L/60’
Continuous flow at 45°C L/h 2458 2751 L/h
Peak flow at 60°C L/10’ 961 1145 L/10’
Peak flow 1st hour at 60°C L/60’ 2124 2438 L/60’
Continuous flow at 60°C L/h 1395 1562 L/h
Coefficient (NL) 67 87

Eco Design Fields

Jumbo 800 Jumbo 1000
Standing loss (Energy label) W 142 154 W
Product Fiche
Jumbo 800 Jumbo 1000
Dimensions A (mm) 1955 2355 (mm)
Dimensions B (mm) 1585 1985 (mm)

Technical brochure

HRs - Jumbo ИНСТРУКЦИЯ ПО УСТАНОВКЕ, ЭКСПЛУАТАЦИИ И СЕРВИСНОМУ ОБСЛУЖИВАНИЮ, для пользователя и сервисного специалиста

6.60MB – ru

HRs 321, 601, 800, 1000 / Jumbo 800, 1000 - Installation, operations and maintenance instructions

6.65MB – en

Ecodesign

Product Fiche

BIM Files

BIM Files

Find an installer

Get in touch with an installer for a free, no obligation estimate.

Call ACV

Need some answers? Talk to a specialist

Tel. +32 2 334 82 20