Next product
Portrait

HeatMaster® 30 N

High performance, combined direct fired boiler and water heater

  • TANK-IN-TANK technology 5 YEAR warranty
  • label_energy_FUEL
  • Boilers
  • DHW Production
  • Standard
  • Floor installation
# GTIN : 5400891032305
# P/N : A1002068
Label 2
  • Stainless steel tank in tank design
  • Can also be used as a stand alone water heater
  • Choice of Burner:
  • - Low NOx premix gas or LPG
  • - Forced draught natural gas or LPG
  • - Pressure jet 28 sec or 35 sec oil
  • Anti-Legionellae: Hot water stored at a consistently high temperature
  • Built in Primary circuit shunt pump (HEP)
  • Body completely insulated in rigid polyurethane foam
  • Stove enameled casing
  • No need for sacrificial anodes
  • Control panel with Control Thermostat, T+P Gauge, Time Clock, Manual reset high limit thermostat, On/Off Switch, Summer/Winter Switch
  • Most heating demands can be met by connecting two or more HeatMasters together
  • Can be used in conjunction with Smart and Jumbo hot water storage tanks, supplying even the largest hot water requirement
  • Vented or unvented use, mains pressure Systempak available
Schematic
  1. Limit thermostat 95 ° C / Thermometer / Thermostat Security 103 ° C.
  2. Domestic cold water inlet.
  3. Removable front casing.
  4. Rigid polyurethane insulation.
  5. Boiler charging pump.
  6. Control Thermostat.
  7. Burner cover.
  8. Burner (not provided)
  9. Flue reduction collar.
  10. Top metal casing.
  11. Heating circuit outlet.
  12. Domestic hot water outlet.
  13. Internal stainless steel tank.
  14. Flue pipes and turbulators
  15. External steel tank containing the primary fluid.
  16. Heating circuit return
  17. Primary circuit drain valve
  18. Combustion chamber
  19. Steel base

Constructive characteristics

HeatMaster® 30 N HeatMaster® 200 N
Capacity (total) L 151 641 L
Capacity (primary) L 68 241 L
Capacity (domestic hot water) L 83 400 L
Capacity expansion tank(s) L 1 x 8 4 x 8 L
Chimney connection Ømm 150 250 Ømm
Connection - heating Ø" 1 ½ F 2 F Ø"
Connection - DHW Ø" 3/4 M 2 M Ø"
Connection - safety valve Ø" 1/2 M 1 M Ø"
Max operating temperature °C 90 90 °C
Water pressure drop boiler at Δt = 20°C mbar 27 118 mbar
Max service pressure heating (primary) bar 3 3 bar
Max service pressure (DHW) bar 8,6 8,6 bar
Weight (empty) kg 220 628 kg

Heating characteristics

HeatMaster® 30 N HeatMaster® 200 N
Heating time from 10 to 90°C min 34 51 min

Combustion

HeatMaster® 30 N HeatMaster® 200 N
Input max (heating) HCV kW 38,8 171,1 kW
Input max (heating) LCV kW 34,9 154 kW
Efficiency at 30% load (EN15502-1) % 95,0 - %
Efficiency (max output) 80/60°C % 90 92 %
NOx class (EN15502) 5 -
Output power max (80/60°C) kW 31,4 141,7 kW

Domestic hot water performance

HeatMaster® 30 N HeatMaster® 200 N
Peak flow at 40°C L/10’ 380 1570 L/10’
Peak flow 1st hour at 40°C L/60’ 1130 4920 L/60’
Continuous flow at 40°C L/h 900 4020 L/h
Peak flow at 45°C L/10’ 320 1350 L/10’
Peak flow 1st hour at 45°C L/60’ 963 4221 L/60’
Continuous flow at 45°C L/h 772 3446 L/h
Peak flow at 60°C L/10’ 201 915 L/10’
Peak flow 1st hour at 60°C L/60’ 651 2925 L/60’
Continuous flow at 60°C L/h 540 2412 L/h

Electrical Characteristics

HeatMaster® 30 N HeatMaster® 200 N
Voltage V 230 230 V
Frequency Hz 50 50 Hz
Protection IP 30 30
Electrical consumption W 82 425 W
Electrical power requirements A 0,4 1,8 A

Technical brochure

Casing Assembly Instructions HM 200

6.81MB – fr en nl pl it de es ru

Addendum HeatMaster 200N-200F (V13)

498.83kB

Burner BG2000-M 201 installation instructions

2.99MB

Burner_assembly_instructions HM 201

2.50MB

Casing Assembly Instructions HeatMaster 201 v17

10.28MB

HM 30-100 N - Technical manual

2.49MB

HeatMaster 201 (v17) - Installation, operations and maintenance instructions

8.33MB – en

HeatMaster (1999) - Installations-, Bedienungs- und Wartungsanleitung

4.82MB – en de

HeatMaster 200 N / 200 F (v13) : Installation, operation and maintenance instructions

3.89MB – en

HeatMaster 200 N / 200 F (v13) : ИНСТРУКЦИЯ ПО УСТАНОВКЕ, ЭКСПЛУАТАЦИИ И СЕРВИСНОМУ ОБСЛУЖИВАНИЮ

3.92MB – ru

HeatMaster 201 Booster - Assembling and installation instructions

723.11kB – en

HeatMaster 71, 101, 201 (v13) - Installation, operations and maintenance instructions

6.07MB – en

HeatMaster 71-101-201 (V13)

6.10MB – ru

HeatMaster N - Installation, operations and maintenance instructions - v2013

4.69MB – ru

HeatMaster N - Installation, operations and maintenance instructions - v2013

4.64MB – en

Find an installer

Get in touch with an installer for a free, no obligation estimate.

Call ACV

Need some answers? Talk to a specialist

Tel. +32 2 334 82 20