Constructive characteristics |
||
---|---|---|
Capacity (total) | 641 | L |
Capacity (primary) | 241 | L |
Capacity (domestic hot water) | 400 | L |
Capacity expansion tank(s) | 4 x 8 | L |
Chimney connection | 250 | Ømm |
Connection - heating | 2 F | Ø" |
Connection - DHW | 2 M | Ø" |
Connection - safety valve | 1 M | Ø" |
Max operating temperature | 90 | °C |
Water pressure drop boiler at Δt = 20°C | 190 | mbar |
Max service pressure heating (primary) | 3 | bar |
Max service pressure (DHW) | 8,6 | bar |
Weight (empty) | 644 | kg |
Heating characteristics |
||
Pre-heating time from 10 to 80°C (Heat source: boiler) | 27 | min |
Heating time from 10 to 90°C | 46 | min |
Combustion |
||
Input max (heating) HCV | 208,9 | kW |
Input max (heating) LCV | 196 | kW |
Combustion efficiency | 93,1 | % |
Efficiency at 30% load (EN15502-1) | 94,5 | % |
Efficiency (max output) 80/60°C | 92 | % |
CO emissions max output | 4 | ppm |
Mass rate of combustion products (gas) | 432 | kg/h |
NOx class (EN15502) | 5 | |
Output power max (80/60°C) | 180 | kW |
Domestic hot water performance |
||
Peak flow at 40°C | 1675 | L/10’ |
Peak flow 1st hour at 40°C | 5976 | L/60’ |
Continuous flow at 40°C | 5161 | L/h |
Peak flow at 45°C | 1444 | L/10’ |
Peak flow 1st hour at 45°C | 5131 | L/60’ |
Continuous flow at 45°C | 4424 | L/h |
Peak flow at 60°C | 961 | L/10’ |
Peak flow 1st hour at 60°C | 3126 | L/60’ |
Continuous flow at 60°C | 2598 | L/h |
Electrical Characteristics |
||
Voltage | 230 | V |
Frequency | 50 | Hz |
Protection IP | 30 | |
Electrical consumption | 815 | W |
Electrical power requirements | 3,5 | A |
Eco Design Fields |
||
Seasonal space heating efficiency (35°C) | 81.8 | % |
Get in touch with an installer for a free, no obligation estimate.
A keyword, a reference, a range, a product,...