Portrait

HeatMaster® 200 F

High performance combined boiler and water heater

  • TANK-IN-TANK TECHNOLOGY
  • label_energy_FUEL
  • Boilers
  • DHW Production
  • Standard
  • Floor installation
# GTIN : 5400891032497
# P/N : A1002097
Label 2
  • Stainless steel tank-in-tank design
  • Comprises a primary circuit which may also be used for a heating circuit.
  • Body completely insulated in 50mm rigid polyurethane foam.
  • Various fuel options, the HeatMaster ® 200 N comes with Gas, Oil, LPG or propane options.
  • The HeatMaster ® 200 F is equipped with matched oil burner adapted to the combustion chamber of the boiler. The burner output on the HM200F model is increased to 196 kilowatts input.
  • Build in primary circuit shunt HEP pumps, Primary expansion vessels, safety valve and low water safety switch.
  • Control panel with main switch, summer / winter switch, time clock, control thermostat and combined temperature and pressure gauge, primary low water pressure indicator, burner lockout indicator, high limit cut off indicator and manual reset high limit thermostat.
Schematic
  1. Flue reducer (vertical output option available).
  2. Domestic cold water inlet.
  3. Thermostat pocket.
  4. Connection for T+P valve ( optional).
  5. Automatic air vent.
  6. Rigid polyurethane foam insulation.
  7. Internal stainless steel tank.
  8. Low water pressure switch.
  9. Thermostat pocket.
  10. Control stat pocket
  11. HEP Boiler charge pump (X2).
  12. Thermostat pocket for ECS probe.
  13. Hot water flow.
  14. Heating flow.
  15. Primary expansion vessel (4x).
  16. Flue ways and turbulators.
  17. Heating return.
  18. Drain valve.
  19. Primary safety valve.
  20. Primary circuit.
  21. Combustion chamber.

Constructive characteristics

Capacity (total) 641 L
Capacity (primary) 241 L
Capacity (domestic hot water) 400 L
Capacity expansion tank(s) 4 x 8 L
Chimney connection 250 Ømm
Connection - heating 2 F Ø"
Connection - DHW 2 M Ø"
Connection - safety valve 1 M Ø"
Max operating temperature 90 °C
Water pressure drop boiler at Δt = 20°C 190 mbar
Max service pressure heating (primary) 3 bar
Max service pressure (DHW) 8,6 bar
Weight (empty) 644 kg

Heating characteristics

Pre-heating time from 10 to 80°C (Heat source: boiler) 27 min
Heating time from 10 to 90°C 46 min

Combustion

Input max (heating) HCV 208,9 kW
Input max (heating) LCV 196 kW
Combustion efficiency 93,1 %
Efficiency at 30% load (EN15502-1) 94,5 %
Efficiency (max output) 80/60°C 92 %
CO emissions max output 4 ppm
Mass rate of combustion products (gas) 432 kg/h
NOx class (EN15502) 5
Output power max (80/60°C) 180 kW

Domestic hot water performance

Peak flow at 40°C 1675 L/10’
Peak flow 1st hour at 40°C 5976 L/60’
Continuous flow at 40°C 5161 L/h
Peak flow at 45°C 1444 L/10’
Peak flow 1st hour at 45°C 5131 L/60’
Continuous flow at 45°C 4424 L/h
Peak flow at 60°C 961 L/10’
Peak flow 1st hour at 60°C 3126 L/60’
Continuous flow at 60°C 2598 L/h

Electrical Characteristics

Voltage 230 V
Frequency 50 Hz
Protection IP 30
Electrical consumption 815 W
Electrical power requirements 3,5 A

Eco Design Fields

Seasonal space heating efficiency (35°C) 81.8 %

Technical brochure

Addendum HeatMaster 200N-200F (V13)

498.83kB

Burner BG2000-M 201 installation instructions

2.99MB

Burner_assembly_instructions HM 201

2.50MB

Casing Assembly Instructions HeatMaster 201 v17

10.28MB

HM 30-100 N - Technical manual

2.49MB

HeatMaster 201 (v17) - Installation, operations and maintenance instructions

8.33MB – en

HeatMaster (1999) - Installations-, Bedienungs- und Wartungsanleitung

4.82MB – en de

HeatMaster 200 N / 200 F (v13) : Installation, operation and maintenance instructions

3.89MB – en

HeatMaster 200 N / 200 F (v13) : ИНСТРУКЦИЯ ПО УСТАНОВКЕ, ЭКСПЛУАТАЦИИ И СЕРВИСНОМУ ОБСЛУЖИВАНИЮ

3.92MB – ru

HeatMaster 201 Booster - Assembling and installation instructions

723.11kB – en

HeatMaster 71, 101, 201 (v13) - Installation, operations and maintenance instructions

6.07MB – en

HeatMaster 71-101-201 (V13)

6.10MB – ru

HeatMaster N - Installation, operations and maintenance instructions - v2013

4.69MB – ru

HeatMaster N - Installation, operations and maintenance instructions - v2013

4.64MB – en

Find an installer

Get in touch with an installer for a free, no obligation estimate.

Call ACV

Need some answers? Talk to a specialist

Tel. +32 2 334 82 20