Previous product
Portrait

HR i 800

Tank in stainless steel with hand hole for installation on the floor.

  • TANK-IN-TANK TECHNOLOGY
  • label_energy_EXT
  • Tanks
  • Floor installation
# GTIN : 5400891036839
# P/N : A1004575
Label 2
  • 100 mm high performance soft insulation PUR foam with vinyl finish and zipper
  • Adjustable feet for fine level adjustment.
  • Primary connections available in the back.
  • 3 models: 318, 606 and 800 liters.
  • Kit with thermostat and thermometer available as an option
  • Anti-Legionella: storage temperature > 60°C
  • Thermostatic mixing valve recommended.
Schematic
  1. Manual air bleed valve
  2. Primary circuit inlet
  3. 100 mm soft insulation (not shown)
  4. Inner stainless steel tank (not shown)
  5. Outer steel tank (primary)
  6. Primary circuit outlet
  7. Cold drink water inlet
  8. DHW outlet
  9. T-connection with Drain valve and Auxiliary DHW loop
  10. Stainless steel drywell (not shown)
  11. Hand hole (not shown)
  12. Foot (x3) for fine level adjustment

Constructive characteristics

HR i 320 HR i 600 HR i 800
Capacity (total) L 318 606 800 L
Capacity (primary) L 55 161 125 L
Weight (empty) kg 127 220 265 kg
Max operating temperature °C 90 90 90 °C
Max operating pressure heating (primary) bar 4 4 4 bar
Max operating pressure (DHW) bar 8,6 8,6 8,6 bar
Primary flow (EN 12897:2016) L/s 1,81 2,08 2,08 L/s
Primary heater pressure drop (EN12897:2016) mbar 99 92 75 mbar
Connection - primary Ø" 2 F 2 F 2 F Ø"
Connection - DHW Ø" 1 ½ M 1 ½ M 1 ½ M Ø"
Connection - re-circulation / safety valve Ø" 3/4 M 3/4 M 3/4 M Ø"

Heating characteristics

HR i 320 HR i 600 HR i 800
Reheat time (EN 12897) min - - - min
Reheat performance (EN 12897:2016) kW 60 71 82 kW
Max absorbed heat (Heat source: boiler) kW 76 88 100 kW

Domestic hot water performance

HR i 320 HR i 600 HR i 800
Peak flow at 40°C L/10’ 922 1345 1881 L/10’
Peak flow 1st hour at 40°C L/60’ 2732 3437 4270 L/60’
Continuous flow at 40°C L/h 2172 2511 2868 L/h
Peak flow at 45°C L/10’ 790 1153 1612 L/10’
Peak flow 1st hour at 45°C L/60’ 2342 2946 3660 L/60’
Continuous flow at 45°C L/h 1862 2152 2458 L/h
Peak flow at 60°C L/10’ 504 706 961 L/10’
Peak flow 1st hour at 60°C L/60’ 1402 1733 2124 L/60’
Continuous flow at 60°C L/h 1077 1232 1395 L/h
Coefficient (NL) 18 34 67

Eco Design Fields

HR i 320 HR i 600 HR i 800
Standing loss (Energy label) W 80.4 112 124.5 W
Product Fiche
HR i 320 HR i 600 HR i 800
Dimensions A (mm) 1800 2095 2122 (mm)
Dimensions B (mm) 559 703 780 (mm)
Dimensions C (mm) 468 458 509 (mm)
Dimensions D (mm) 1498 1786 1759 (mm)
Dimensions E (mm) 142 144 132 (mm)

Technical brochure

GL / HR / HR BE / JUMBO (1999)

3.88MB – en de

HRi 320, 600, 800 - Installation, operations and maintenance instructions - v2017

4.04MB – en

Technical manual kit thermostat soft jacket (A1004714 - 027000)

2.01MB

Thermostat mounting kit

506.07kB

ИНСТРУКЦИЯ ПО УСТАНОВКЕ, ЭКСПЛУАТАЦИИ И СЕРВИСНОМУ ОБСЛУЖИВАНИЮ, для пользователя и сервисного специалиста - v2017

4.01MB – ru

Marketing brochure

ACV Guide to Ecodesign and Energy Labelling

969.34kB – en

Ecodesign

Product Fiche

BIM Files

BIM Files

Find an installer

Get in touch with an installer for a free, no obligation estimate.

Call ACV

Need some answers? Talk to a specialist

Tel. +32 2 334 82 20