Portrait

Jumbo 800

Fast recovery, high volume Tank-in-Tank hot water storage

  • Tank-In-Tank Technology
  • label_energy_EXT
  • Tanks
  • Floor installation
# GTIN : 5400891002698
# P/N : 06648501
Label 2
Label 3
  • Tank-in-Tank floor standing indirect hot water storage tank.
  • Stainless steel construction - no need for sacrificial anodes.
  • High performance - fast heat up and rapid recovery.
  • Fully insulated - 120mm Rock wool insulation.
  • Stove enameled steel casing, supplied seperatley to enable the tank to pass through standard 800mm doorways.
  • Two sizes - 800 and 1000 litres.
  • Can be used in battery formation for high output installations.
  • Vented or unvented use, with mains pressure SystemPak available.
  • Large heating surface area means reduced boiler cycling.
  • Anti-Legionella : Storage temperature > 60 ° C.
Schematic
  1. Hot water outlet.
  2. Domestic cold water inlet.
  3. Thermometer.
  4. Control thermostat.
  5. Rockwool insulation - 120 mm.
  6. Stove enameled metal casing.
  7. Domestic Hot Water return /T+P Valve tapping
  8. Primary water flow connection
  9. Outer steel tank containing the primary fluid.
  10. Thermostat pocket
  11. Internal stainless steel tank.
  12. Primary water return connection

Constructive characteristics

Capacity (total) 800 L
Capacity (primary) 125 L
Weight (empty) 360 kg
Max operating temperature 85 °C
Max operating pressure heating (primary) 4 bar
Max operating pressure (DHW) 8,6 bar
Primary flow (EN 12897:2016) 2,08 L/s
Primary heater pressure drop (EN12897:2016) 75 mbar
Connection - primary 2 F Ø"
Connection - DHW 1 ½ M Ø"
Connection - re-circulation / safety valve 1 ½ M Ø"

Heating characteristics

Reheat time (EN 12897:2016) - min
Reheat performance (EN 12897:2016) 82 kW
Max absorbed heat (Heat source: boiler) 100 kW

Domestic hot water performance

Peak flow at 40°C 1881 L/10’
Peak flow 1st hour at 40°C 4270 L/60’
Continuous flow at 40°C 2868 L/h
Peak flow at 45°C 1612 L/10’
Peak flow 1st hour at 45°C 3660 L/60’
Continuous flow at 45°C 2458 L/h
Peak flow at 60°C 961 L/10’
Peak flow 1st hour at 60°C 2124 L/60’
Continuous flow at 60°C 1395 L/h
Coefficient (NL) 67

Eco Design Fields

Standing loss (Energy label) 142 W
Product Fiche
Dimensions A 1955 (mm)
Dimensions B 1585 (mm)